Specification table of integral LPG supply stations:
Items/Model
|
Main items
|
Tank
|
Hydrocarbon pump
|
Vaporization
|
LKZ0503DD-LPG
|
5m3
|
canned-motor pump
|
single pump
|
Electric heating type
|
hot -water type
|
LKZ1003DD-LPG
|
10m3
|
canned-motor pump
|
single pump
|
Electric heating type
|
hot -water type
|
LKZ2003DD-LPG
|
20m3
|
canned-motor pump
|
single pump
|
Electric heating type
|
hot -water type
|
Main functions:
1、Two phases of gas and liquid input 2、Power pack leakage protection 3、Automatic spray
4、Wholly explosion-proof electrical equipments 5、Liquid level indicator 6、Auto unloaded
7、If gas leakage is beyond the limits, the power should be off automatically. 8、Temperature indicator
9、Auto filling 10、Two-stage gas leakage alarm 11、Pressure indicator
12、If the liquid level is too high or too low, there is alarm to tell you automatically. 13、Electrical heater
14、Exhaust air 15、If the liquid level is too high or too low, pumps would be closed automatically
16、Multilayer filter 17、Emergency cutoff
Main specifications:
1、Installation type: integration 2、Dimension(L×W×H, Unit: mm) 3、5m3:7000×1600×2800
4、10m3:7700×1900×3200 5、20m3:8300×2100×3400
6、Whole Weight (Kg): 5m3: 3800 10m3:4600 20m3:6000
7、Design pressure of tank: 1.8MPa 8、Working pressure of tank: 1.62MPa 9、Open pressure of safety valve: 1.75MPa
10、Flow of canned-motor pump: 6m3/h 11、Input power of canned-motor pump: 6.0Kw
12、Rated revolution: 2780r/min 13、Canned-motor pump head: 90m 14、Power supply: AC380V
15、Vaporization capacity: 10-1000Kg/h 16、No. of gas monitoring site: 2
17、Alarm of gas leakage: second degree of gas density for alarm is 20% of 2% of minimum gas density leading to explosion. First degree of gas density for alarm is 50% of 2% of minimum gas density leading to explosion.
Starting temperature for auto spray:≥42℃
Shout down temperature for auto spray:≤38℃
High level of liquid alarm: ≥85% of tank volume.
Low level of liquid alarm: ≥15% of tank volume.