We supply high quality station post insulators according to IEC ,ANSI,standard and customers' specfications .
IEC standard product types including : C8-550 , C8-1050 , C10-1175, C12.5-1800 etc.
ANSI standard post insulators including: TR202, TR205, TR208,TR216, TR286, TR304 etc.
The station post insulator can be made upto 1000KV , 30KN .
The shapping method in both Isostatic pressing and wet process are all available .
IEC Designation
|
|
C12.5-150
|
C4-170
|
C4-200
|
C6-200
|
C4-250
|
C6-325
|
Figure
|
|
1
|
1
|
1
|
1
|
1
|
1
|
Overal Height(H),
|
mm
|
355
|
445
|
475
|
475
|
560
|
770
|
Max. Shed Diameter(D)
|
mm
|
205
|
180
|
180
|
190
|
175
|
195
|
Creepage Distance
|
mm
|
660
|
850
|
950
|
950
|
1200
|
1600
|
Top Fitting P.C.D.(d1)/Hole pattern
|
mm
|
Φ76/M12(4x)
|
Φ76/M12(4x)
|
Φ76/M12(4x)
|
Φ76/M12(4x)
|
Φ76/M12(4x)
|
Φ127/M16(4x)
|
Bottom Fitting P.C.D.(d2)/Hole pattern
|
mm
|
Φ76/M12(4x)
|
Φ76/M12(4x)
|
Φ76/M12(4x)
|
Φ76/M12(4x)
|
Φ127/M16(4x)
|
Φ127/M16(4x)
|
Min. Cantilever Strength
|
kN
|
12.5
|
4
|
4
|
6
|
4
|
6
|
Min. Torsion Strength
|
N-m
|
2.5
|
1.2
|
1.2
|
1.8
|
1.8
|
2.5
|
Power Frequency Withstand Wet
|
kV
|
50
|
70
|
70
|
70
|
95
|
140
|
Lightning Impulse Withstand Dry
|
kV
|
150
|
170
|
200
|
200
|
250
|
325
|
IEC Designation
|
|
C16-1050-Ⅲ
|
C10-1050-Ⅱ
|
C8-1050-Ⅲ
|
C12.5-1050-Ⅲ
|
C10-1425-Ⅱ
|
Figure
|
|
1
|
1
|
1
|
1
|
1
|
Overal Height(H),
|
mm
|
2300
|
2300
|
2400
|
2300
|
3150
|
Max. Shed Diameter(D)
|
mm
|
330
|
275
|
285
|
315
|
290
|
Creepage Distance
|
mm
|
6300
|
6000
|
6300
|
6300
|
8400
|
Top Fitting P.C.D.(d1)/Hole pattern
|
mm
|
Φ127/M16(4x)
|
Φ127/M16(4x)
|
Φ127/M16(4x)
|
Φ254/Φ8(8x)
|
Φ127/M16(4x)
|
Bottom Fitting P.C.D.(d2)/Hole pattern
|
mm
|
Φ300/Φ18(8x)
|
Φ275/Φ18(8x)
|
Φ254/Φ18(8x)
|
Φ225/Φ8(8x)
|
Φ300/Φ18(8x)
|
Min. Cantilever Strength
|
kN
|
16
|
10
|
8
|
12.5
|
10
|
Min. Torsion Strength
|
N-m
|
10
|
4
|
6
|
10
|
6
|
Power Frequency Withstand Wet
|
kV
|
460
|
460
|
460
|
460
|
950
|
Lightning Impulse Withstand Dry
|
kV
|
1050
|
1050
|
1050
|
1050
|
1425
|
Net Weight
|
kgs
|
269
|
207
|
210
|
25
|
300
|
HIVOLT station post insulators choose high quality materials :
1 Metal flange the flange use high density ductile iron or malleable iron ,every pieces test qualified after magnetic powder inspection .
Flange surface are hot galvanized , zinc thickness meet related IEC and ASTM standard requirement
2 Porcelain the insulation part use high aluminum porcelain C130 , the porcelain surface covered a layer of hard and shinning glaze , color can be grey , brown or white .
3 Cement excellent Portland cement make the assembled insulator have very good mechanical performance and the quality more reliable .
4 silicone sealant we sue a layer of silicone sealant cover the cement ring surface , just to protect cement have a stable performance for longer life ,
In the meantime , it can prevent cement dust fall down to pollute the electrical instrument .
one more thing , we can also paint HRTV on the insulator body surface , if customer has such requirement .
the HRTV coating has excellent insulation performance , it can be used in extra heavy pollution area.